Protection grade: IP20
Ambient temperature: -5°C to +40°C
Ambient humidity: ≤50%
Altitude: ≤2000m
Mounting category: III
Model | LC1-D09 | LC1-D12 | LC1-D18 | LC1-D25 | LC1-D32 | LC1-D40 | LC1-D50 | LC1-D65 | LC1-D80 | LC1-D95 | |
---|---|---|---|---|---|---|---|---|---|---|---|
Rated working current (A) | AC3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
AC4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | |
Thermal current (A) | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 95 | 110 | |
Standard power ratings of threephase motors in AC-3 category (kW) | 220/230V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 |
380/400V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | |
415V | 4 | 5.5 | 9 | 11 | 15 | 22 | 25 | 37 | 45 | 45 | |
500V | 5.5 | 7.5 | 10 | 15 | 18.5 | 22 | 30 | 37 | 55 | 55 | |
660/690V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 33 | 37 | 45 | 55 | |
Electrical life in AC3 (x104) | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 | |
Electrical life in AC4 (x104) | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | |
Mechanical life (x104) | 1000 | 1000 | 1000 | 1000 | 800 | 800 | 800 | 800 | 600 | 600 |
Dimensions
Model | A | B | C | D | E | a | b | Φ |
---|---|---|---|---|---|---|---|---|
LC1-D09/12 | 47 | 76 | 82 | 113 | 133 | 34/35 | 50/60 | 4.5 |
LC1-D18 | 47 | 76 | 87 | 118 | 138 | 34/35 | 50/60 | 4.5 |
LC1-D25 | 57 | 86 | 95 | 126 | 146 | 40 | 48 | 4.5 |
LC1-D32 | 57 | 86 | 100 | 131 | 151 | 40 | 48 | 4.5 |
LC1-D40-65 | 77 | 129 | 116 | 145 | 165 | 40 | 100/110 | 6.5 |
LC1-D80/95 | 87 | 129 | 127 | 175 | 195 | 40 | 100/110 | 6.5 |